F5YH 5*1.5//MAT

Description

Description

Standards

  • International
    IEC 60332-1-2
  • National
    BS 6360

CONSTRUCTION

2.1 Conductor

Plain, annealed copper conductors, circular flexible conductor, conforming to the applicable requirements of BS 6360.

2.2 Insulation

PVC.

2.3 Sheath

HIGHLY FLEXIBLE THERMOPLASTIC RUBBER 105 DEGREE.

TEST AT WORKS - BS 7919:2001

Routine Tests                                                       

 -          Absence of faults in the insulation :    acc. to BS 7919  parag. 7.8.2         

 -          Max. DC conductors resistance at 20°C acc. to BS 7919 parag. 6.8.2 7.8.5         

                                                                       

Liban Cables will carry out these tests on all the lengths and tests certificates will be provided                                                                 

                                                                       

  Sample tests                                                              

            Check of the build - up and color coding of the cable                                                      

            Check of dimensions                                                    

            Insulation          :           according to BS 7919                 Parag. 7.2.3

            Sheath  :                       according to BS 7919                 Parag. 7.6.3

                                                                       

                                                                       

These tests will be carried out on one length of the order                                                            

Tests certificates will be provided by Liban Cables

Characteristics

Characteristics

Construction characteristics

Construction characteristics

Conductor material
Copper class 5
Conductor shape
Circular
Number of conductors
5
Insulation
PVC
Outer sheath
TPR (thermoplastic rubber)

Dimensional characteristics

Dimensional characteristics

Conductor cross-section
1.5 mm²
Nominal insulation thickness
0.7 mm
Nominal outer sheath thickness
1.0 mm
Nominal outer diameter
10.0 mm
Approximate weight
139 kg/km

Electrical characteristics

Electrical characteristics

Max. DC resistance of the conductor at 20°C
13.3 Ohm/km
Permissible current rating in open air
18 A
Rated Voltage Uo/U (Um)
0,6/1 kV

Usage characteristics

Usage characteristics

Operating temperature, range
-15 ... 55 °C
Installation temperature, range
-5 ... 50 °C
Ambient air temperature
30 °C
Max. conductor temperature in service
70 °C
Short-circuit max. conductor temperature
160 °C
Flame retardant
IEC 60332-1-2
Oil resistance
Yes
U.V resistance
Yes

Resources

Resources

Contact us

Topics on which you wish to get more informations:

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close